The compartments shall be separated from each other by a smoke barrier in accordance with Section 709. Penetrations between the two compartments shall be limited to plumbing and electrical piping and conduit that are firestopped in accordance with Section 714. Doorways shall be protected by fire door assemblies that comply with Section 716, automatic-closing by smoke detection in accordance with Section 716.2.6.6 and installed in accordance with NFPA 105 and Section 716.2.2.1. Where provided, each compartment shall have an air supply and an exhaust system independent of the other compartments.
Upcodes Diagrams

Related Code Sections

714.5.4 Fire and Smoke Protection Features, Penetrations in Smoke Barriers
Penetrations in smoke barriers shall be protected by an approved through-penetration firestop system installed and tested in accordance ...
714.5.4 Fire and Smoke Protection Features, Penetrations in Smoke Barriers
Penetrations in smoke barriers shall be protected by an approved through-penetration firestop system installed and tested in accordance ...
607.5.4 Duct Systems, Corridors/Smoke Barriers
for the operation and control of the system. Smoke dampers are not required in smoke barrier penetrations where the openings in ducts are limited to a single ...