// CODE SNIPPET
[F] 910.3.2 Smoke and Heat Vent Locations
Go To Full Code Chapter
Smoke and heat vents shall be located 20 feet (6096 mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm) or more from fire barriers. Vents shall be uniformly located within the roof in the areas of the building where the vents are required to be installed by Section 910.2 with consideration given to roof pitch, sprinkler location and structural members.
Upcodes Diagrams
Related Code Sections
910.3.2 Fire Protection and Life Safety Systems, Smoke and Heat Vent Locations
Smoke and heat vents shall be located 20 feet (6096 mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm) or more from fire ...
910.3.2 Fire Protection and Life Safety Systems, Smoke and Heat Vent Locations
Smoke and heat vents shall be located 20 feet (6096 mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm) or more from fire ...
Section 311 General Regulations, Smoke and Heat Vents
Approved smoke and heat vents shall be installed in the roofs of one-story buildings where required by the International Fire Code. Smoke and heat ...
9.2.17.1 Sprinkler Location Requirements,
Skylights that allow venting, other than smoke and heat venting per 20.6.5, shall be provided with sprinkler protection installed in the skylight ...
9.2.17 Sprinkler Location Requirements, Skylights
Skylights that allow venting, other than smoke and heat venting per 20.6.5, shall be provided with sprinkler protection installed ...