// CODE SNIPPET
710.5.2.2 Smoke and Draft Control Doors
Go To Full Code Chapter
Where required elsewhere in the code, doors in smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot [0.015424 m3/(s × m2)] of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature test and the elevated temperature exposure test. Installation of smoke doors shall be in accordance with NFPA 105.
710.5.2.2.1 Smoke and Draft Control Door Labeling
Smoke and draft control doors complying only with UL 1784 shall be permitted to show the letter "S" on the manufacturer's labeling.
Related Code Sections
710.5.2.2 Fire and Smoke Protection Features, Smoke and Draft Control Doors
Where required elsewhere in the code, doors in smoke partitions shall meet the requirements for a smoke and draft control door assembly tested ...
710.5.2.2 Fire and Smoke Protection Features, Smoke and Draft Control Doors
Where required elsewhere in the code, doors in smoke partitions shall meet the requirements for a smoke and draft control door assembly tested ...
716.2.9.3 Fire and Smoke Protection Features, Smoke and Draft Control Door Labeling Requirements
Smoke and draft control doors complying with UL 1784 shall be labeled in accordance with Section 716.2.9.1 and shall show the letter "S" on the fire ...
716.2.9.3 Fire and Smoke Protection Features, Smoke and Draft Control Door Labeling Requirements
Smoke and draft control doors complying with UL 1784 shall be labeled in accordance with Section 716.2.9.1 and shall show the letter "S" on the fire ...
3007.6.3 Elevators and Conveying Systems, Lobby Doorways
shall be provided with a 3/4-hour fire door assembly complying with Section 716. The fire door assembly shall comply with the smoke and draft control ...