1009.3 Sloped Entries
JUMP TO FULL CODE CHAPTER
Sloped entries shall comply with 1009.3.
Advisory 1009.3 Sloped Entries. Personal wheelchairs and mobility devices may not be appropriate for submerging in water. Some may have batteries, motors, and electrical systems that when submerged in water may cause damage to the personal mobility device or wheelchair or may contaminate the pool water. Providing an aquatic wheelchair made of non-corrosive materials and designed for access into the water will protect the water from contamination and avoid damage to personal wheelchairs or other mobility aids.
Sloped entries shall extend to a depth of 24 inches (610 mm) minimum and 30 inches (760 mm) maximum below the stationary water level. Where landings are required by 405.7, at least one landing shall be located 24 inches (610 mm) minimum and 30 inches (760 mm) maximum below the stationary water level.
EXCEPTION: In wading pools, the sloped entry and landings, if provided, shall extend to the deepest part of the wading pool.
![]() |
At least two handrails complying with 505 shall be provided on the sloped entry. The clear width between required handrails shall be 33 inches (840 mm) minimum and 38 inches (965 mm) maximum.
EXCEPTIONS:
- Handrail extensions specified by 505.10.1 shall not be required at the bottom landing serving a sloped entry.
- Where a sloped entry is provided for wave action pools, leisure rivers, sand bottom pools, and other pools where user access is limited to one area, the handrails shall not be required to comply with the clear width requirements of 1009.3.3.
- Sloped entries in wading pools shall not be required to provide handrails complying with 1009.3.3. If provided, handrails on sloped entries in wading pools shall not be required to comply with 505.
![]() |
Related Code Sections
1009.3 Recreation Facilities, Sloped Entries
Sloped entries shall comply with 1009.3. Advisory 1009.3 Sloped Entries. Personal wheelchairs and mobility devices may not be appropriate ...
2010 ADA Standards > 10 Recreation Facilities > 1009 Swimming Pools, Wading Pools, and Spas > 1009.3 Sloped Entries
242.3 Scoping Requirements, Wading Pools
At least one accessible means of entry shall be provided for wading pools. accessible means of entry shall comply with sloped entries complying ...
2010 ADA Standards > 2 Scoping Requirements > 242 Swimming Pools, Wading Pools, and Spas > 242.3 Wading Pools
242.2 Scoping Requirements, Swimming Pools
with 1009.2; sloped entries complying with 1009.3; transfer walls complying with 1009.4; transfer systems complying with 1009.5; and pool stairs complying ...
2010 ADA Standards > 2 Scoping Requirements > 242 Swimming Pools, Wading Pools, and Spas > 242.2 Swimming Pools
1009 Recreation Facilities, Swimming Pools, Wading Pools, and Spas
Where provided, pool lifts, sloped entries, transfer walls, transfer systems, and pool stairs shall comply with 1009 ...
(i) 28 CFR 35.151 New Construction and Alterations, Curb Ramps
Newly constructed or altered streets, roads, and highways must contain curb ramps or other sloped areas at any intersection having curbs or other ...