704.1 Slope of Horizontal Drainage Piping
JUMP TO FULL CODE CHAPTER
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than that indicated in Table 704.1.
TABLE 704.1
SLOPE OF HORIZONTAL DRAINAGE PIPE
SIZE (inches) | MINIMUM SLOPE (inch per foot) |
21/2 or less | 1/4 |
3 to 6 | 1/8 |
8 or larger | 1/16 |
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.
Related Code Sections
704.1 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than ...
2014 FBC - Plumbing, 5th edition > 7 Sanitary Drainage > 704 Drainage Piping Installation > 704.1 Slope of Horizontal Drainage Piping
704.1 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than ...
2017 FBC - Plumbing, 6th edition > 7 Sanitary Drainage > 704 Drainage Piping Installation > 704.1 Slope of Horizontal Drainage Piping
704.1 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than ...
2020 FBC - Plumbing, 7th edition > 7 Sanitary Drainage > 704 Drainage Piping Installation > 704.1 Slope of Horizontal Drainage Piping
713.3.2 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be designed and installed at slopes in accordance with Table 704.1 ...
2020 FBC - Plumbing, 7th edition > 7 Sanitary Drainage > 713 Computerized Drainage Design > 713.3 Selections of Drainage Pipe Sizes > 713.3.2 Slope of Horizontal Drainage Piping
714.3.2 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be designed and installed at slopes in accordance with Table 704.1 ...
2014 FBC - Plumbing, 5th edition > 7 Sanitary Drainage > 714 Computerized Drainage Design > 714.3 Selections of Drainage Pipe Sizes > 714.3.2 Slope of Horizontal Drainage Piping