// CODE SNIPPET
P3110.3 Slope and Size of Horizontal Branch
Go To Full Code Chapter
The slope of the vent section of the horizontal branch drain shall be not greater than 1 unit vertical in 12 units horizontal (8-percent slope). The entire length of the vent section of the horizontal branch drain shall be sized for the total drainage discharge to the branch in accordance with Table P3005.4.1.
Upcodes Diagrams
Related Code Sections
914.3 Vents, Slope and Size of Horizontal Branch
The slope of the vent section of the horizontal branch drain shall be not greater than one unit vertical in 12 units horizontal (8.3-percent slope ...
P3110.3 Vents, Slope and Size of Horizontal Branch
The slope of the vent section of the horizontal branch drain shall be not greater than 1 unit vertical in 12 units horizontal (8-percent slope). The ...
P3110.3 Vents, Slope and Size of Horizontal Branch
The slope of the vent section of the horizontal branch drain shall be not greater than one unit vertical in 12 units horizontal (8-percent slope ...
P3005.4 Sanitary Drainage, Drain Pipe Sizing
TABLE P3005.4.1
MAXIMUM FIXTURE UNITS ALLOWED TO BE CONNECTED TO BRANCHES AND STACKS
NOMINAL PIPE SIZE (inches)
ANY HORIZONTAL FIXTURE ...
P3005.4 Sanitary Drainage, Drain Pipe Sizing
TABLE P3005.4.1
MAXIMUM FIXTURE UNITS ALLOWED TO BE CONNECTED TO BRANCHES AND STACKS
NOMINAL PIPE SIZE (inches)
ANY HORIZONTAL FIXTURE ...