The thickness of slabs with sloping soffits (see Figure 722.2.2.1.2) shall be determined at a distance 2t or 6 inches (152 mm), whichever is less, from the point of minimum thickness, where t is the minimum thickness.

For SI: 1 inch = 25.4 mm.
FIGURE 722.2.2.1.2
DETERMINATION OF SLAB THICKNESS FOR SLOPING SOFFITS
Upcodes Diagrams

Related Code Sections

722.2.2 Fire and Smoke Protection Features, Concrete Floor and Roof Slabs
The thickness of slabs with sloping soffits (see Figure 722.2.2.1.2) shall be determined at a distance 2t or 6 inches (152 mm), whichever ...
8.2.5 Two-Way Slabs,
A shear cap, where used to increase the critical section for shear at a slab-column joint, shall project below the slab soffit and extend ...