C402.2.5 Slabs-on-grade perimeter insulation

Energy Conservation Code 2015 of Utah > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.2 Specific building thermal envelope insulation requirements (Prescriptive) > C402.2.5 Slabs-on-grade perimeter insulation
JUMP TO FULL CODE CHAPTER

Where the slab on grade is in contact with the ground, the minimum thermal resistance (R-value) of the insulation around the perimeter of unheated or heated slab-on-grade floors designed in accordance with the R-value method of Section C402.1.3 shall be as specified in Table C402.1.3. The insulation shall be placed on the outside of the foundation or on the inside of the foundation wall. The insulation shall extend downward from the top of the slab for a minimum distance as shown in the table or to the top of the footing, whichever is less, or downward to at least the bottom of the slab and then horizontally to the interior or exterior for the total distance shown in the table. Insulation extending away from the building shall be protected by pavement or by not less than of 10 inches (254 mm) of soil.

Exception: Where the slab-on-grade floor is greater than 24 inches (61 mm) below the finished exterior grade, perimeter insulation is not required.

Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


C402.2.5 [CE] Commercial Energy Efficiency, Slabs-on-grade perimeter insulation
Where the slab on grade is in contact with the ground, the minimum thermal resistance ( R -value) of the insulation around the perimeter of unheated ...
Energy Conservation Code 2015 of Utah > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.2 Specific building thermal envelope insulation requirements (Prescriptive) > C402.2.5 Slabs-on-grade perimeter insulation
C303.2.1 [CE] General Requirements, Protection of Exposed Foundation Insulation
Insulation applied to the exterior of basement walls, crawlspace walls and the perimeter of slab-on-grade floors shall have a rigid, opaque ...
Energy Conservation Code 2015 of Utah > 3 [CE] General Requirements > C303 Materials, Systems and Equipment > C303.2 Installation > C303.2.1 Protection of Exposed Foundation Insulation
R303.2.1 [RE] General Requirements, Protection of Exposed Foundation Insulation
Insulation applied to the exterior of basement walls, crawlspace walls and the perimeter of slab-on-grade floors shall have a rigid, opaque ...
Energy Conservation Code 2015 of Utah > 3 [RE] General Requirements > R303 Materials, Systems and Equipment > R303.2 Installation > R303.2.1 Protection of Exposed Foundation Insulation
N1101.11.1 [RE] Energy Efficiency, (R303.2.1) Protection of Exposed Foundation Insulation
Insulation applied to the exterior of basement walls, crawlspace walls and the perimeter of slab-on-grade floors shall have a rigid, opaque ...
Residential Code 2015 of Utah > 11 [RE] Energy Efficiency > N1101 GENERAL > N1101.11 (R303.2) Installation > N1101.11.1 (R303.2.1) Protection of Exposed Foundation Insulation
R402.2.10 [RE] Residential Energy Efficiency, Slab-On-Grade Floors
Slab-on-grade floors with a floor surface less than 12 inches (305 mm) below grade shall be insulated in accordance with Table R402.1.2. The ...
Energy Conservation Code 2015 of Utah > 4 [RE] Residential Energy Efficiency > R402 Building Thermal Envelope > R402.2 Specific Insulation Requirements (Prescriptive) > R402.2.10 Slab-On-Grade Floors
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US