1225.5.1.4.1 Skilled Nursing Facilities
JUMP TO FULL CODE CHAPTER
- Recreation room. Each floor of each building accommodating six or more patients shall be provided with a recreation room with a minimum of 100 square feet (9.29 m2).
- Recreation and dining. A minimum of 100 square feet (9.29 m2) plus 12 square feet (1.11 m2) per bed shall be provided for recreation and dining activities.
Related Code Sections
1225.5.1.4.1 Interior Environment, Skilled Nursing Facilities
Recreation room. Each floor of each building accommodating six or more patients shall be provided with a recreation room with a minimum of 100 square ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.1 Medical Model > 1225.5.1.4 Activity Programming Space > 1225.5.1.4.1 Skilled Nursing Facilities
1225.5.1.4.1 Interior Environment, Skilled Nursing Facilities
Recreation room. Each floor of each building
accommodating six or more patients shall be
provided with a recreation room with a minimum
of 100 ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.1 Medical Model > 1225.5.1.4 Activity Programming Space > 1225.5.1.4.1 Skilled Nursing Facilities
1225.5.1.4.1 Interior Environment, Skilled Nursing Facilities
Recreation room. Each floor of each building accommodating six or more patients shall be provided with a recreation room with a minimum of 100 square ...
California Building Code 2022 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing Andintermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.1 Medical Model > 1225.5.1.4 Activity Programming Space > 1225.5.1.4.1 Skilled Nursing Facilities
1225.1.1 Interior Environment, Small House Skilled Nursing Facilities
Skilled
nursing facilities participating in the Small House Nursing
Facilities Pilot Program established by and in conformance
with Section 1323.5 ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.1 Scope > 1225.1.1 Small House Skilled Nursing Facilities
1225.4.3.4 Interior Environment, Small House Skilled Nursing Facilities
Small
house skilled nursing facility units may provide the
administration and public spaces, medical record storage
and the nursing director's office ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.4 Common Elements > 1225.4.3 Administration Space > 1225.4.3.4 Small House Skilled Nursing Facilities