Manifolds shall be sized in accordance with Table P2903.8.1. Total gallons per minute is the demand for all outlets.
TABLE P2903.8.1
MANIFOLD SIZINGa
PLASTIC METALLIC
Nominal Size ID (inches) Maximumb gpm Nominal Size ID (inches) Maximumb gpm
3/4 17 3/4 11
1 29 1 20
11/4 46 11/4 31
11/2 66 11/2 44
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m, 1 foot per second = 0.3048 m/s.
  1. See Table P2903.6 for w.s.f.u and Table P2903.6(1) for gallon-per-minute (gpm) flow rates.
  2. Based on velocity limitation: plastic, 12 feet per second; metal, 8 feet per second.