803.1 Single Appliance Vent Table 803.1.2(1) Through Table 803.1.2(6)
Table 803.1.2(1) through Table 803.1.2(6) shall
not be used where obstructions arc installed in the venting
system. The installation of vents serving listedappliances with vent dampers shall be in accordance with the appliance manufacturer's
installation instructions or in accordance with the
following:
The maximum capacity of the vent system shall be determined
using the NAT Max column.
The minimum capacity shall be determined as though the
appliance were a fan-assisted appliance, using the FAN
Min column to determine the minimum capacity of the
vent system. Where the corresponding "FAN Min" is
"NA", the vent configuration shall not be permitted and
an alternative venting configuration shall be utilized.
[NFPA 54:13.1.1]
803.1.1 Vent Downsizing
Where the vent size determined
from the tables is smaller than the appliancedraft hood outlet or flue collar, the use of the smaller size shall
be permitted provided that the installation is in accordance
with the following requirements:
The total vent height (H) is not less than 10 feet
(3048 mm).
Vents for appliancedraft hood outlets or flue collars
12 inches (305 mm) in diameter or smaller are not
reduced more than one table size.
Vents for appliancedraft hood outlets or flue collars
exceeding 12 inches (305 mm) in diameter are not
reduced more than two table sizes.
The maximum capacity listed in the tables for a fan-assisted
appliance is reduced by 10 percent (0.90 x
maximum table capacity).
The draft hood outlet exceeds 4 inches (102 mm) in
diameter. A 3 inch (76 mm) diameter vent shall not
be connected to a 4 inch (102 mm) diameter draft
hood outlet. This provision shall not apply to fan-assisted
appliances. [NFPA 54:13.1.2]
803.1.2 Elbows
Single-appliance venting configurations with zero lateral lengths in Table 803.1.2(1), Table
803.1.2(2), and Table 803.1.2(5) shall not have elbows
in the venting system. Single-appliance venting with
lateral lengths, include two 90 degree (1.57 rad) elbows.
For each additional elbow up to and including 45 degrees
(0.79 rad), the maximum capacity listed in the venting
tables shall be reduced by 5 percent. For each additional
elbow greater than 45 degrees (0.79 rad) up to and
including 90 degrees (1.57 rad), the maximum capacity
listed in the venting tables shall be reduced by 10
percent. Where multiple offsets occur in a vent, the total lateral length of offsets combined shall not exceed that
specified in Table 803.1.2(1) through Table 803.1.2(5).
[NFPA 54:13.1.3]
99% Winter Design Temperatures for the Contiguous United States
This map is a necessarily generalized guide to temperatures in the contiguous United States. Temperatures shown for areas
such as mountainous regions and large urban centers may not be accurate. The data used to develop this map are from the
1993 ASHRAE Handbook - Fundamentals (Chapter 24, Table 1: Climate Conditions for the United States).
For 99% winter design temperatures in Alaska, consult the ASHRAE Handbook - Fundamentals.
99% winter design temperatures for Hawaii are greater than 37°F.
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
Notes: 1 See Figure 803.1.2(6) for a map showing local 99 percent winter design temperatures in the United States. 2 NA: Not applicable.
803.1.3 Zero Lateral
Zero lateral (L) shall apply to a straight vertical vent attached to a top outlet draft hood or
flue collar. [NFPA 54:13.1.4]
803.1.4 High-Altitude Installations
Sea level input ratings shall be used where determining maximum capacity
for high-altitude installation. Actual input (derated for altitude)
shall be used for determining minimum capacity for
high-altitude installation. [NFPA 54:13.1.5]
803.1.5 Multiple Input Ratings
For appliances with more than one input rate, the minimum vent capacity
(FAN Min) determined from the tables shall be less than
the lowest appliance input rating, and the maximum vent
capacity (FAN Max/NAT Max) determined from the
tables shall exceed the highest appliance rating input.
[NFPA 54:13.1.6]
803.1.6 Corrugated Chimney Liner Reduction
Listed corrugated metallic chimney liner systems in masonry
chimneys shall be sized by using Table 803.1.2(1) or
Table 803.1.2(2) for Type B vents, with the maximum
capacity reduced by 20 percent (0.80 x maximum
capacity) and the minimum capacity as shown in Table
803.1.2(1) or Table 803.1.2(2).
Corrugated metallic liner systems installed with bends
or offsets shall have their maximum capacity further
reduced in accordance with Section 803.1.2. The 20
percent reduction for corrugated metallic chimney liner
systems includes an allowance for one long radius 90
degree (1.57 rad) turn at the bottom of the liner. [NFPA
54:13.1.7]
803.1.7 Connection to Chimney Liners
Connections
between chimney liners and listed double-wall connectors
shall be made with listed adapters designed for such
purpose. [NFPA 54:13.1.8]
803.1.8 Vertical Vent Upsizing Using 7 X Rule
Where
the vertical vent has a larger diameter than the vent
connector, the vertical vent diameter shall be used to determine
the minimum vent capacity, and the connector diameter
shall be used to determine the maximum vent capacity.
The flow area of the vertical vent shall not exceed seven
times the flow area of the listedappliance categorized vent
area, flue collar area, or draft hood outlet area unless
designed in accordance with approved engineering
methods. [NFPA 54:13.1.9]
Table
803.1.2(1) through Table 803.1.2(5) shall be used for
chimneys and vents not exposed to the outdoors below
the roof line. A Type B vent or listedchimney lining
system passing through an unused masonry chimney flue
shall not be considered to be exposed to the outdoors.
Where vents extend outdoors above the roof more than 5
feet (1524 mm) higher than required by Table 802.6.2,
and where vents terminate in accordance with Section
802.6.2(1), the outdoor portion of the vent shall be
enclosed as required by this section for vents not considered
to be exposed to the outdoors or such venting
system shall be engineered. A Type B vent passing
through an unventilated enclosure or chase insulated to a
value of not less than R-8 shall not be considered to be
exposed to the outdoors. Table 803.1.2(3) in combination
with Table 803.1.2(6) shall be used for clay-tile-lined
exterior masonry chimneys, provided the following
requirements are met:
The vent connector is Type B double wall.
The vent connector length is limited to 18
inches/inch (18 mm/mm) of vent connector diameter.
Clay flue lining shall be manufactured in accordance with ASTM C315 or
other approvedstandard.
803.1.11.2 Chimney Lining
Chimney lining shall be listed in accordance with UL 1777.
803.1.12 Corrugated Vent Connector Size
Corrugated vent connectors shall not be smaller than the listedappliance
categorized vent diameter, flue collar diameter, or
draft hood outlet diameter. [NFPA 54:13.1.12]
803.1.13 Upsizing
Vent connectors shall not be upsized more than two sizes exceeding the listedappliance categorized
vent diameter, flue collar diameter, or draft hood
outlet diameter. [NFPA 54:13.1.13]
803.1.14 Single Run of Vent
In a single run of vent or vent connector, more than one diameter and type shall
be permitted to be used, provided that the sizes and types
are permitted by the tables. [NFPA 54:13.1.14]
803.1.15 Interpolation
Interpolation shall be permitted in calculating capacities for vent dimensions that fall
between table entries. [NFPA 54:13.1.15]
803.1.16 Extrapolation
Extrapolation beyond the table entries shall not be permitted. [NFPA 54:13.1.16]
803.1.17 Engineering Methods
For vent heights lower than 6 feet (1829 mm) and exceeding vent heights shown
in the tables, engineering methods shall be used to calculate
vent capacities. [NFPA 54:13.1.17]
803.1.18 Height Entries
Where the actual height of a vent falls between entries in the height column of the
applicable table in Table 803.1.2(1) through Table
803.1.2(6), one of the following shall be used:
Interpolation.
The lower appliance input rating shown in the table
entries; for FAN MAX and NAT MAX column
values and the higher appliance input rating for the
FAN MIN column values. [NFPA 54:13.1.18]
size of the lowest connector and of the vertical vent
leading to the lowest interconnection of a multistory
system shall be in accordance with Table ...