604.5 Size of Fixture Supply
JUMP TO FULL CODE CHAPTER
The minimum size of a fixture supply pipe shall be as shown in Table 604.5. The fixture supply pipe shall terminate not more than 30 inches (762 mm) from the point of connection to the fixture. A reduced-size flexible water connector installed between the supply pipe and the fixture shall be of an approved type. The supply pipe shall extend to the floor or wall adjacent to the fixture. The minimum size of individual distribution lines utilized in gridded or parallel water distribution systems shall be as shown in Table 604.5.
MINIMUM SIZES OF FIXTURE WATER SUPPLY PIPES
FIXTURE | MINIMUM PIPE SIZE (inch) |
Bathtubsa (60" × 32" and smaller) | 1/2 |
Bathtubsa (larger than 60" × 32") | 1/2 |
Bidet | 3/8 |
Combination sink and tray | 1/2 |
Dishwasher, domestica | 1/2 |
Drinking fountain | 3/8 |
Hose bibbs | 1/2 |
Kitchen sinka | 1/2 |
Laundry, 1, 2 or 3 compartmentsa | 1/2 |
Lavatory | 3/8 |
Shower, single heada | 1/2 |
Sinks, flushing rim | 3/4 |
Sinks, service | 1/2 |
Urinal, flush tank | 1/2 |
Urinal, flushometer valve | 3/4 |
Wall hydrant | 1/2 |
Water closet, flush tank | 3/8 |
Water closet, flushometer tank | 3/8 |
Water closet, flushometer valve | 1 |
Water closet, one piecea | 1/2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.
- Where the developed length of the distribution line is 50 feet or less, and the available pressure at the meter is 35 psi or greater, the minimum size of an individual distribution line supplied from a manifold and installed as part of a parallel water distribution system shall be one nominal tube size smaller than the sizes indicated.
Related Code Sections
C404.5.1 [CE] Commercial Energy Efficiency, Maximum Allowable Pipe Length Method
The maximum allowable piping length from the nearest source of heated water to the termination of the fixture supply pipe shall be in accordance ...
Energy Conservation Code 2018 of Colorado > 4 [CE] Commercial Energy Efficiency > C404 Service Water Heating (Mandatory) > C404.5 Heated Water Supply Piping > C404.5.1 Maximum Allowable Pipe Length Method
C404.5.1 [CE] Commercial Energy Efficiency, Maximum Allowable Pipe Length Method
The maximum allowable piping length from the nearest source of heated water to the termination of the fixture supply pipe shall be in accordance ...
Energy Conservation Code 2015 of Colorado > 4 [CE] Commercial Energy Efficiency > C404 Service Water Heating (Mandatory) > C404.5 Efficient Heated Water Supply Piping > C404.5.1 Maximum Allowable Pipe Length Method
402.6 Equipment for General Use, Minimum Size
Fixture wires shall not be smaller than 18 AWG ...
National Electrical Code 2020 of Colorado > 4 Equipment for General Use > 402 Fixture Wires > 402.6 Minimum Size
(A) Special Equipment, Size
Where a transformer supplies an electric motor driven fire pump, it shall be rated at a minimum of 125 percent of the sum of the fire pump motor(s ...
National Electrical Code 2020 of Colorado > 6 Special Equipment > 695 Fire Pumps > 695.5 Transformers > (A) Size
(A) Special Equipment, Size
The minimum conductor size shall be not less than 28 AWG for electronic signal circuits and not less than 26 AWG for electromagnetic valve supply ...
National Electrical Code 2020 of Colorado > 6 Special Equipment > 650 Pipe Organs > 650.6 Conductors > (A) Size