The equipment bonding jumper on the load side of an overcurrent devices shall be sized, as a minimum, in accordance with Table E3908.12, but shall not be required to be larger than the circuit conductors supplying the equipment. An equipment bonding conductor shall be not smaller than No. 14 AWG.
A single common continuous equipment bonding jumper shall be permitted to connect two or more raceways or cables where the bonding jumper is sized in accordance with Table E3908.12 for the largest overcurrent device supplying circuits therein.

Related Code Sections

E3908.19 Power and Lighting Distribution, Size of Equipment Bonding Jumper on Load Side
of an overcurrent device. The equipment bonding jumper on the load side of an overcurrent devices shall be sized, as a minimum, in accordance ...
(6) Wiring Methods and Materials, Bonding Jumpers
Where parallel equipment bonding jumpers or supply-side bonding jumpers are installed in raceways, they shall be sized and installed in accordance ...
Section E3609 Services, Bonding
supply-side bonding jumper and main bonding jumper. The bonding jumper shall ...