1010.1.1 Size of Doors
Go To Full Code Chapter
The required capacity of each door opening shall be sufficient for the occupant load thereof and shall provide a minimum clear opening width of 32 inches (813 mm). The clear opening width of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees (1.57 rad). Where this section requires a minimum clear opening width of 32 inches (813 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a minimum clear opening width of 32 inches (813 mm). In Group I-2, doors serving as means of egress doors where used for the movement of beds shall provide a minimum clear opening width of 411/2 inches (1054 mm). The minimum clear opening height of doors shall be not less than 80 inches (2032 mm).
Exceptions:
- In Group R-2 and R-3 dwelling and sleeping units that are not required to be an Accessible unit, Type A unit or Type B unit, the minimum width shall not apply to door openings that are not part of the required means of egress.
- In Group I-3, door openings to resident sleeping units that are not required to be an Accessible unit shall have a minimum clear opening width of 28 inches (711 mm).
- Door openings to storage closets less than 10 square feet (0.93 m2) in area shall not be limited by the minimum clear opening width.
- The maximum width of door leaves in revolving doors that comply with Section 1010.3.1 shall not be limited.
- The maximum width of door leaves in power-operated doors that comply with Section 1010.3.2 shall not be limited.
- Door openings within a dwelling unit or sleeping unit shall have a minimum clear opening height of 78 inches (1981 mm).
- In dwelling and sleeping units that are not required to be Accessible, Type A or Type B units, exterior door openings other than the required exit door shall have a minimum clear opening height of 76 inches (1930 mm).
- In Groups I-1, R-2, R-3 and R-4, in dwelling and sleeping units that are not required to be Accessible, Type A or Type B units, the minimum clear opening widths shall not apply to interior egress doors.
- Door openings required to be accessible within Type B units intended for user passage shall have a minimum clear opening width of 31.75 inches (806 mm).
- Doors to walk-in freezers and coolers less than 1,000 square feet (93 m2) in area shall have a maximum width of 60 inches (1524 mm) nominal.
- Doors serving nonaccessible single-user shower or sauna compartments, toilet stalls or dressing, fitting or changing rooms shall have a minimum clear opening width of 20 inches (508 mm).
1010.1.1.1 Projections Into Clear Opening
There shall not be projections into the required clear opening width lower than 34 inches (864 mm) above the floor or ground. Projections into the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102 mm).
Exception: Door closers, overhead door stops, power door operators, and electromagnetic door locks shall be permitted to be 78 inches (1980 mm) minimum above the floor.
Upcodes Diagrams
Related Code Sections
1010.1.1 Means of Egress, Size of Doors
The required capacity of each door opening shall be sufficient for the occupant load thereof and shall provide a minimum clear opening width of 32 ...
1010.1.1 Means of Egress, Size of Doors
The required capacity of each door opening shall be sufficient for the occupant load thereof and shall provide a minimum clear opening width of 32 ...
410.5.2 Accessible Routes, Platform Lifts With Doors on Adjacent Sides
depth of 60 inches (1525 mm) minimum.
FIGURE 410.5.2.1
PLATFORM LIFTS - SIZE WITH DOORS ON ADJACENT SIDES NEW BUILDINGS ...
410.5.1 Accessible Routes, Lifts With Single Door or Doors on Opposite Ends
(915 mm) minimum and a clear floor depth of 48 inches (1220 mm) minimum.
FIGURE 410.5.1.2
PLATFORM LIFTS - SIZE WITH SINGLE DOOR OR DOORS ON ...
Section 410 Accessible Routes, Platform Lifts
depth of 48 inches (1220 mm) minimum.
FIGURE 410.5.1.1
PLATFORM LIFTS - SIZE WITH SINGLE DOOR OR DOORS ON OPPOSITE ENDS - NEW BUILDINGS ...