710.5 Size of Building Drains and Sewers
Go To Full Code Chapter
Building drains or building sewers receiving a discharge from a pump or ejector shall be adequately sized to prevent overloading. Two fixture units shall be allowed for each gallon per minute (L/s) of flow.
Related Code Sections
710.5 Sanitary Drainage, Size of Building Drains and Sewers
Building drains or building sewers receiving a discharge from a pump or ejector shall be adequately sized to prevent overloading. Two fixture units ...
C 601.9 Alternate Plumbing Systems, Sizing Building Drains and Sewers
In a single-stack vent system, the building drain and branches thereof shall be sized in accordance with Table 703.2, and the building sewer shall ...
C 304.2 Alternate Plumbing Systems, Size of Building Drain and Building Sewer
The maximum number of drainage fixture units allowed on the building drain or building sewer of a given size shall be in accordance with Table C ...
717.0 Sanitary Drainage, Size of Building Sewers
The minimum size of a building sewer shall be determined on the basis of the total number of fixture units drained by such sewer, in accordance ...
P3005.4.2 Sanitary Drainage, Building Drain and Sewer Size and Slope