Section P-1110 Size, Length and Number of Vents and Fresh Air Inlets

Go To Full Code Chapter
P-1110.1 Length of Vents
The length of a vent shall be its developed length from the lowest connection of the vent with the soil stack, waste stack, or house drain to the vent terminal above the roof.
P-1110.2 Size of Stack Vent
The diameter of a stack vent shall not be less than the diameter of the soil or waste stack of which it is an extension.
P-1110.3 Size of Vent Stacks
A vent stack or main vent connecting relief vents, circuit vents, or loop vents shall have a diameter of at least one-half the diameter of the soil or waste stack to which the vent stack or main vent is connected, but in no case less than 1-1/2 inches. The maximum number of fixture units connected to the vent stack shall be in accordance with Table P-1110.4. The vent stack or main vent shall not be less in size than the branch, circuit, or loop vent it is servicing. Where fixtures are installed on the house drain behind the line of vent, a minimum vent stack of 1-1/2 inches shall be required for small fixtures having a fixture unit value not greater than 10 and a minimum of 2 inches for one or more water closets and other fixtures, except if a larger size is required according to Table P-1110.4.

Figure P-1110.3


VENT STACK SIZING
P-1110.4 Size of Relief Vent
The diameter of a relief vent shall not be less than one-half the diameter of the horizontal branch to which it is connected, with a minimum size of 1-1/2 inches. The maximum number of fixture units connected to the relief vent shall be in accordance with Table P-1110.4.

Figure P-1110.4



RELIEF VENT SIZING


TABLE P-1110.4 — SIZE AND LENGTH OF VENTS
Fixture Units
Connected
Diameter of Vent (inches) — Maximum Length of Vent (feet)
11/2" 2" 21/2" 3" 4" 5" 6" 8"
13 75 310
26 70 300
47 35 140 450
72 23 85 260 650
98 18 75 240 600
195 30 95 240 1000
293 22 70 180 750
390 28 70 320 1000
624 20 50 240 750
969 20 95 240 1000
1320 18 70 180 750
2165 30 80 350 1000
3016 25 60 250 900
3959 40 120 450
4501 30 80 350
5850 25 60 250
Upcodes Diagrams

Related Code Sections

P-1110.1 Vents and Venting, Length of Vents
The length of a vent shall be its developed length from the lowest connection of the vent with the soil stack, waste stack, or house drain ...
P-509.3 Traps, Cleanouts, Interceptors, and Backwater Valves, Vents
Every oil interceptor shall have a separate vent on the terminal end of the inlet piping and a fresh air inlet on the sewer side of the interceptor ...
P-1106.1 Vents and Venting, Fresh Air Inlet Required
inlet. The size of the fresh air inlet shall be 4 inches for 4-inch, 5-inch, and 6-inch drain pipe and 6 inches for 8-inch drains discharging ...
P-1106.3 Vents and Venting, Sumps
All sumps receiving the discharge from fixtures other than water closets shall be provided with a fresh air inlet pipe. The size of the fresh air ...
P-502.1 Traps, Cleanouts, Interceptors, and Backwater Valves, Size
for 15-inch drains with 10-inch standpipe. Where two fresh air inlets are used, connections shall be made by use of a wye on the standpipe. Vents larger ...