509.2.2.2 Size and Location
Go To Full Code Chapter
The baffle plate shall be sized and located so that flames or combustion gases shall travel a distance not less than 18 inches (457 mm) from the heat source to the grease removal device. [NFPA 96:6.2.2.3]
Related Code Sections
509.2.2.2 Exhaust Systems, Size and Location
The baffle plate shall be sized and located so that flames or combustion gases shall travel a distance not less than 18 inches (457 mm) from the heat ...