  1. Site-specific investigations shall include adequate borings and/or cone penetration tests (CPTs) and other appropriate field methods, to enable the determination of geotechnical parameters.
  2. Adequate coverage of subsurface data, both horizontally and vertically, shall be obtained to develop geotechnical parameters.
  3. Exploration shall be deep enough to characterize subsurface materials that are affected by embankment behavior and shall extend to depth of at least 20 feet below the deepest foundation depth.
  4. During field exploration, particular attention shall be given to the presence of continuous low-strength layers or thin soil layers that could liquefy or weaken during the design earthquake shaking.
  5. CPTs provide continuous subsurface profile and shall be used to complement exploratory borings. When CPTs are performed, at least one boring shall be performed next to one of the CPT soundings to check that the CPT-soil behavior type interpretations are reasonable for the site. Any difference between CPT interpretation and subsurface condition obtained from borings shall be reconciled.
  6. Quantitative site soil stratigraphy is required to a depth of 100 feet for assigning a site class (see Table 31F-6-1).
  7. Laboratory tests may be necessary to supplement the borings and insitu field tests.
Upcodes Diagrams

Related Code Sections

3106F.2.2 [SLC] Marine Oil Terminals, Site-Specific Information
Site-specific investigations shall include adequate borings and/or cone penetration tests (CPTs) and other appropriate field methods, to enable ...
3106F.2.2 [SLC] Marine Oil Terminals, Site-Specific Information
Site-specific investigations shall include adequate borings and/or cone penetration tests (CPTs) and other appropriate field methods, to enable ...
3106F.2 [SLC] Marine Oil Terminals, Site Characterization
Site characterization shall be based on site-specific geotechnical information. If existing information is used, the geotechnical engineer of record ...