Where site-specific procedures are used to determine the maximum considered earthquake ground motion response spectrum, the design spectral response acceleration, Sa, at any period shall be determined from Equation 16-48:

Sa = 2/3 SaM                      (Equation 16-48)

and shall be greater than or equal to 80 percent of the design spectral response acceleration, Sa, determined by the general response spectrum in Section 1615.1.4.