E3902.7 Sink Receptacles
Go To Full Code Chapter
125-volt through 250-volt receptacles that are located within 6 feet (1829 mm) of the top inside edge of the bowl of the sink and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(7)]
Upcodes Diagrams
Related Code Sections
E3902.7 Power and Lighting Distribution, Sink Receptacles
125-volt through 250-volt receptacles that are located within 6 feet (1829 mm) of the top inside edge of the bowl of the sink and supplied by single ...
(B) Special Occupancies, Ground-Fault Circuit Interrupters (GFCI)
Bathrooms, including receptacles in luminaires
Kitchens, where receptacles are installed to serve countertop surfaces
Sinks, where receptacles ...
(C) Special Occupancies, Ground-Fault Circuit-Interrupter Protection
locations:
Where the receptacles are installed to serve kitchen countertop surfaces
Within 1.8 m (6 ft) of any lavatory or sink
Exception: Receptacles ...
(C) Wiring and Protection, Countertops and Work Surfaces
In kitchens, pantries, breakfast rooms, dining rooms, and similar areas of dwelling units, receptacle outlets for countertop and work surfaces ...
(C) Special Occupancies, Ground-Fault Circuit-Interrupter Protection
1.8 m (6 ft) of any lavatory or sink
Exception No. 1: Receptacles installed for appliances in dedicated spaces, such as for disposals, refrigerators ...