UpCodes logo
Go To Full Code Chapter
For single supply systems, where the air supplied to a ventilation zone is a mixture of outdoor air and system-level recirculated air, zone ventilation efficiency (Evz) shall be determined in accordance with Equation 404.3.1. Examples of single supply systems include constant-volume reheat, singleduct VAV, single-fan dual-duct, and multizone systems.

Evz = 1+Xs-Zpz (Equation 404.3.1)

The average outdoor air fraction for the system (Xs) shall be determined in accordance with Equation 404.2 and the primary outdoor air fraction for the zone (Zpz) shall be determined in accordance with Section 403.5.1. [ASHRAE 62.1:A1.2.1]
Upcodes Diagrams

Related Code Sections

404.3.1 Ventilation Air, Single Supply Systems
For single supply systems, where the air supplied to a ventilation zone is a mixture of outdoor air and system-level recirculated air, zone ...
(D) Wiring and Protection, Size
Where a separately derived system supplies more than a single enclosure, the system bonding jumper for each enclosure shall be sized ...
22.12.1.1 Special Occupancy Requirements,
The design of fire water supply and distribution systems, where used, shall provide for the simultaneous supply of those fixed fire protection ...