605.11.1.2.3 Single-Ridge Roofs
Go To Full Code Chapter
Panels and modules installed on Group R-3 buildings with a single ridge shall be located in a manner that provides two, 3-foot-wide (914 mm) access pathways from the eave to the ridge on each roof slope where panels and modules are located.
Exception:
This requirement shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
Related Code Sections
605.11.1.2.3 Building Services and Systems, Single-Ridge Roofs
Panels and modules installed on Group R-3 buildings with a single ridge shall be located in a manner that provides two, 3-foot-wide (914 mm) access ...
1205.2.1.1 Energy Systems, Pathways to Ridge
Not fewer than two 36-inch-wide (914 mm) pathways on separate roof planes, from lowest roof edge to ridge, shall be provided on all buildings. Not ...