510.1 Single Appliance Vent Table 510.1.2(1) Through Table 510.1.2(6)
Go To Full Code ChapterSee More
Venting Table 510.1.2(1) through Table 510.1.2(6) shall not be used where obstructions are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer's instructions or in accordance with the following:
- The maximum capacity of the vent system shall be determined using the "NAT Max" column.
- The minimum capacity shall be determined as though the appliance were a fan-assisted appliance, using the "FAN Min" column to determine the minimum capacity of the vent system. Where the corresponding "FAN Min" is "NA," the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. [NFPA 54:13.1.1]
510.1.1 Vent Downsizing
Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the use of the smaller size shall be permitted, provided that the installation complies with all of the following requirements:
- The total vent height (H) is at least 10 feet (3048 mm).
- Vents for appliance draft hood outlets or flue collars 12 inches (300 mm) in diameter or smaller are not reduced more than one table size.
- Vents for appliance draft hood outlets or flue collars larger than 12 inches (300 mm) in diameter are not reduced more than two table sizes.
- The maximum capacity listed in the tables for a fan-assisted appliance is reduced by 10 percent (0.90 × maximum table capacity).
- The draft hood outlet is greater than 4 inches (100 mm) in diameter. A 3 inch (80 mm) diameter vent shall not be connected to a 4 inch (100 mm) diameter draft hood outlet. This provision shall not apply to fan-assisted appliances. [NFPA 54:13.1.2]
Related Code Sections
510.1 Water Heaters, Single Appliance Vent Table 510.1.2(1) Through Table 510.1.2(6)
Venting Table 510.1.2(1) through Table 510.1.2(6) shall not be used where obstructions are installed in the venting system. The installation of vents ...
510.1.5 Water Heaters, Multiple Input Ratings
For appliances with more than one input rate, the minimum vent capacity (FAN Min) determined from Table 510.1.2(1) through Table 510.2(9) shall ...
510.1.10 Water Heaters, Chimney and Vent Locations
Table 510.1.2(1) through Table 510.1.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. A Type B vent ...
510.1.16 Water Heaters, Engineering Methods
For vent heights lower than 6 feet (1829 mm) and higher than shown in Table 510.1.2(1) through Table 510.2(9), engineering methods shall be used ...
510.1.11 Water Heaters, Corrugated Vent Connector Size
Corrugated vent connectors shall not be smaller than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet ...