// CODE SNIPPET
E 503.5.5 Simultaneous Heating and Cooling Limitation, Zone Controls
Go To Full Code Chapter
Zone thermostatic controls shall prevent the following:
- Reheating.
- Recooling.
- Mixing or simultaneously supplying air that has been previously mechanically heated and air that has been previously cooled, either by mechanical cooling or by economizer systems.
- Other simultaneous operation of heating and cooling systems to the same zone.
Exceptions:
- Zones for which the volume of air that is reheated, recooled, or mixed is less than the larger of the following:
- Twenty percent of the zone design peak supply for systems with DDC and 30 percent for other systems.
- The outdoor airflow rate required to be in accordance with the ventilation requirements of Chapter 4 or ASHRAE 62.1 for the zone.
- A higher rate that is capable of demonstrating, to the satisfaction of the Authority Having Jurisdiction, to reduce overall system annual energy usage by offsetting reheat or recool energy losses through a reduction in outdoor air intake for the system.
- The airflow rate required to be in accordance with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates.
- Zones with DDC that comply with the following:
- The airflow rate in dead band between heating and cooling does not exceed the larger of the following:
- Twenty percent of the zone design peak supply rate.
- The outdoor airflow rate required to be in accordance with the ventilation requirements of Chapter 4 or ASHRAE 62.1 for the zone.
- A higher rate that is capable of demonstrating, to the satisfaction of the Authority Having Jurisdiction, to reduce overall system annual energy usage by offsetting reheat or recool energy losses through a reduction in outdoor air intake.
- The airflow rate required in accordance with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates.
- The airflow rate that is reheated, recooled, or mixed shall be less than 50 percent of the zone design peak supply rate.
- The first stage of heating consists of modulating the zone supply air temperature setpoint up to a maximum setpoint while the airflow is maintained at the dead band flow rate.
- The second stage of heating consists of modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate.
- The airflow rate in dead band between heating and cooling does not exceed the larger of the following:
- Laboratory exhaust systems in accordance with Section E 503.5.11.3.
- Zones where not less than 75 percent of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered (including condenser heat) or site-solar energy source. [ASHRAE 90.1:6.5.2.1]
E 503.5.5.1 Supply Air Temperature Reheat Limit
Where reheating is permitted in accordance with this appendix, zones that have both supply and return or exhaust air openings more than 6 feet (1829 mm) above the floor shall not supply heating air more than 20°F (11°C) above the space temperature setpoint.
Exceptions:
- Laboratory exhaust systems in accordance with Section E 503.5.11.3.
- During preoccupancy building warm-up and setback. [ASHRAE 90.1:6.5.2.1.1]
E 503.5.5.2 Hydronic System Controls
The heating of fluids in hydronic systems that have been previously mechanically cooled and the cooling of fluids that have been previously mechanically heated shall be limited in accordance with Section E 503.5.5.2.1 through Section E 503.5.5.2.3. [ASHRAE 90.1:6.5.2.2]
E 503.5.5.2.1 Three-Pipe System
Hydronic systems that use a common return system for both hot water and chilled water shall not be used. [ASHRAE 90.1:6.5.2.2.1]
E 503.5.5.2.2 Two-Pipe Changeover System
Systems that use a common distribution system to supply both heated and chilled water are acceptable where in accordance with the following:
- The system is designed to allow a dead band between changeover from one mode to the other of not less than 15°F (8°C) outdoor air temperature.
- The system is designed to operate and is provided with controls that will allow operation in one mode for not less than 4 hours before changing over to the other mode.
- Reset controls are provided that allow heating and cooling supply temperatures at the changeover point to be not more than 30°F (17°C) apart. [ASHRAE 90.1:6.5.2.2.2]
E 503.5.5.2.3 Hydronic (Water Loop) Heat Pump Systems
Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g., boiler) shall have the following:
- Controls that are capable of and configured to provide a heat pump water supply temperature dead band of not less than 20°F (11°C) between initiation of heat rejection and heat addition by the central devices (e.g., tower and boiler).
- For climate zone 3 through zone 8, where a closed-circuit tower (fluid cooler) is used, either an automatic valve shall be installed to bypass all but a minimal flow of water around the tower (for freeze protection) or low-leakage positive closure dampers shall be provided. Where an open-circuit tower is used directly in the heat pump loop, an automatic valve shall be installed to bypass heat pump water flow around the tower. Where an open-circuit tower is used in conjunction with a separate heat exchanger to isolate the tower from the heat pump loop, then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop.
Exception: Where a system loop temperature optimization controller is used to determine the most efficient operating temperature based on real-time conditions of demand and capacity, dead bands of less than 20°F (11°C) shall be permitted. [ASHRAE 90.1:6.5.2.2.3]
E 503.5.5.3 Dehumidification
Where humidity controls are provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream.
Exceptions:
- The system is capable of and configured to reduce supply air volume to 50 percent or less of the design airflow rate or the minimum outdoor air ventilation rate in accordance with ASHRAE 62.1 or other applicable federal, state, or local code or recognized standard, whichever is larger before simultaneous heating and cooling takes place.
- The individual fan cooling unit has a design cooling capacity of not more than 65 000 Btu/h (19 kW) and is capable of and configured to unload to 50 percent capacity before simultaneous heating and cooling takes place.
- The individual mechanical cooling unit has a design cooling capacity of not more than 40 000 Btu/h (11.7 kW). An individual mechanical cooling unit is a single system composed of a fan or fans and a cooling coil capable of providing mechanical cooling.
- Systems serving spaces where specific humidity levels are required to satisfy process needs, such as vivariums, museums, surgical suites, pharmacies, and buildings with refrigerating systems, such as supermarkets, refrigerated warehouses, and ice arenas, and where the building includes site-recovered energy or site solar energy that provide energy equal to 75 percent or more of the annual energy for reheating or for providing warm air in mixing systems. This exception shall not apply to computer rooms.
- Not less than 90 percent of the annual energy for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or site-solar energy.
- Systems where the heat added to the airstream is the result of the use of a desiccant system and 75 percent of the heat added by the desiccant system is removed by a heat exchanger, either before or after the desiccant system with energy recovery. [ASHRAE 90.1:6.5.2.3]
E 503.5.5.4 Humidifier Preheat
Humidifiers with preheating jackets mounted in the airstream shall be provided with an automatic valve to shut off preheat where humidification is not required. [ASHRAE 90.1:6.5.2.4.1]
E 503.5.5.4.1 Insulation
Humidification system dispersion tube hot surfaces in the airstreams of ducts or air-handling units shall be insulated with a product with an insulating value of not less than R-0.5.
Exception: Systems where mechanical cooling, including economizer operation, does not occur simultaneously with humidification. [ASHRAE 90.1:6.5.2.4.2]
E 503.5.5.5 Preheat Coils
Preheat coils shall have controls that stop their heat output where mechanical cooling, including economizer operation, is occurring. [ASHRAE 90.1:6.5.2.5]
Upcodes Diagrams
Related Code Sections
E 503.5.5 Sustainable Practices, Simultaneous Heating and Cooling Limitation, Zone Controls
Zone thermostatic controls shall prevent the following:
Reheating.
Recooling.
Mixing or simultaneously supplying air that has been previously ...
6.5.2.1.1 Heating, Ventilating, and Air Conditioning, Supply Air Temperature Reheat Limit
Where reheating is permitted by other parts of this standard, zones that have both supply and return/exhaust air openings greater than 6 ft above ...
E 503.5.5.4.1 Sustainable Practices, Insulation
with an insulating value of not less than R-0.5. Exception: Systems where mechanical cooling, including economizer operation, does not occur simultaneously ...
Uniform Mechanical Code 2018 of Nevada > E Sustainable Practices > E 503.0 Heating, Ventilation, and Air-Conditioning — Other Than Low-Rise Residential Buildings > E 503.5 Prescriptive Path, Economizers > E 503.5.5 Simultaneous Heating and Cooling Limitation, Zone Controls > E 503.5.5.4 Humidifier Preheat > E 503.5.5.4.1 Insulation
E 503.5.5.2.3 Sustainable Practices, Hydronic (Water Loop) Heat Pump Systems
Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g ...
Uniform Mechanical Code 2018 of Nevada > E Sustainable Practices > E 503.0 Heating, Ventilation, and Air-Conditioning — Other Than Low-Rise Residential Buildings > E 503.5 Prescriptive Path, Economizers > E 503.5.5 Simultaneous Heating and Cooling Limitation, Zone Controls > E 503.5.5.2 Hydronic System Controls > E 503.5.5.2.3 Hydronic (Water Loop) Heat Pump Systems
E 503.5.5.2.2 Sustainable Practices, Two-Pipe Changeover System
to the other mode.
Reset controls are provided that allow heating and cooling supply temperatures at the changeover point to be not more than 30°F (17°C) apart ...
Uniform Mechanical Code 2018 of Nevada > E Sustainable Practices > E 503.0 Heating, Ventilation, and Air-Conditioning — Other Than Low-Rise Residential Buildings > E 503.5 Prescriptive Path, Economizers > E 503.5.5 Simultaneous Heating and Cooling Limitation, Zone Controls > E 503.5.5.2 Hydronic System Controls > E 503.5.5.2.2 Two-Pipe Changeover System