Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to a central supervising station or when approved by the Fire Department, shall sound an audible signal at a constantly attended location.
Exceptions:
  1. Underground key or hub valves in roadway boxes provided by the city or a public utility are not required to be monitored.
  2. Backflow prevention device test valves, located in limited area sprinkler system supply piping, shall be locked in the open position. In occupancies required to be equipped with a fire alarm system, the backflow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated.
Upcodes Diagrams

Related Code Sections

903.4.1 Fire Protection Systems, Signals and Monitoring
Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to a central supervising station or when ...
903.4.1 Fire Protection Systems, Signals and Monitoring
Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to a central supervising station or when ...
27.4.3.4 Public Emergency Alarm Reporting Systems,
Fire alarm signals, other emergency alarm signals, and monitoring for integrity signals shall be permitted on the same radio frequency, dedicated ...
26.3.3.2 Supervising Station Alarm Systems,
Signal monitoring, retransmission, and associated recordkeeping and reporting shall be provided by a company that has a listing for central station ...