R905.2.8.3 Sidewall Flashing
JUMP TO FULL CODE CHAPTER
Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. Where anchored masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and counterflashing shall be provided in accordance with Section R703.8.2.2. Where exterior plaster or adhered masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and Section R703.6.3.
Related Code Sections
R905.2.8.3 Roof Assemblies, Sidewall Flashing
Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches ...
Residential Code 2018 of Kansas > 9 Roof Assemblies > R905 Requirements for Roof Coverings > R905.2 Asphalt Shingles > R905.2.8 Flashing > R905.2.8.3 Sidewall Flashing
R903.2.1 Roof Assemblies, Locations
flashing shall be installed to divert the water away from where the eave of a sloped roof intersects a vertical sidewall. Where flashing is of metal ...
Residential Code 2018 of Kansas > 9 Roof Assemblies > R903 Weather Protection > R903.2 Flashing > R903.2.1 Locations
3.6.2.5 Definitions, Sidewall Sprinkler.
A sprinkler having special deflectors that are designed to discharge most of the water away from the nearby wall in a pattern resembling one-quarter ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 3 Definitions > 3.6 Sprinkler Definitions > 3.6.2 Installation Orientation > 3.6.2.5 Sidewall Sprinkler.
1404.10.1.2 Exterior Walls, Flashing
Flashing shall comply with the applicable requirements of Section 1404.4 and the following ...
Building Code 2018 of Kansas > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.10 Adhered Masonry Veneer > 1404.10.1 Exterior Adhered Masonry Veneer > 1404.10.1.2 Flashing
1404.4 Exterior Walls, Flashing
Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect that moisture to the exterior. Flashing ...
Building Code 2018 of Kansas > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.4 Flashing