[F] 415.11.8.2.2 Shutoff of Gas Supply
Go To Full Code Chapter
The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for which gas is detected when a short-term hazard condition is detected. Automatic closure of shutoff valves shall comply with the following:
- Where the gas detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close.
- Where the gas detection sampling point initiating the gas detection system alarm is within a room and compressed gas containers are not in gas cabinets or an exhausted enclosure, the shutoff valves on all gas lines for the specific gas detected shall automatically close.
- Where the gas detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve supplying the manifold for the compressed gas container of the specific gas detected shall automatically close.
Exception: Where the gas detection sampling point initiating the gas detection system alarm is at the use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold, the shutoff valve for the branch line located in the piping distribution manifold enclosure shall automatically close.
Upcodes Diagrams
Related Code Sections
415.11.7.2.2 Special Detailed Requirements Based on Occupancy and Use, Shutoff of Gas Supply
The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being ...
415.11.8.2.2 Special Detailed Requirements Based on Occupancy and Use, Shutoff of Gas Supply
The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being ...
7.9.7* Installation and Environmental Considerations,
Where the gas supply is connected to the building gas supply system, it shall be connected on the supply side of the main gas shutoff valve ...
7.9.7* Installation and Environmental Considerations,
Where the gas supply is connected to the building gas supply system, it shall be connected on the supply side of the main gas shutoff valve ...
415.11.8 Special Detailed Requirements Based on Occupancy and Use, Gas Detection Systems
detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored ...