(B) Shutdown of Prime Mover
Go To Full Code Chapter
Generators shall have provisions to shut down the prime mover. The means of shutdown shall comply with all of the following:
- Be equipped with provisions to disable all prime mover start control circuits to render the prime mover incapable of starting
- Initiate a shutdown mechanism that requires a mechanical reset