L 402.6 Showerheads
Go To Full Code Chapter
Showerheads shall not exceed 2.0 gpm (7.6 L/m) at 80 psi (552 kPa), and shall be listed to ASME A112.18.1/CSA B125.1 and the EPA WaterSense Specification for Showerheads.
L 402.6.1 Multiple Showerheads Serving One Shower Compartment
The total allowable flow rate of water from multiple showerheads flowing at a given time, with or without a diverter, including rain systems, waterfalls, bodysprays, and jets, shall not exceed 2.0 gpm (7.6 L/m) per shower compartment, where the floor area of the shower compartment is less than 1800 square inches (1.161 m2). For each increment of 1800 square inches (1.161 m2) of floor area after that or part thereof, additional showerheads are allowed, provided the total flow rate of water from flowing devices shall not exceed 2.0 gpm (7.6 L/m) for each such increment.
Exceptions:
- Gang showers in nonresidential occupancies. Singular showerheads or multiple shower outlets serving one showering position in gang showers shall not have more than 2.0 gpm (7.6 L/m) total flow.
- Where provided, shower compartments required for persons with disabilities in accordance with Chapter 17 shall not have more than 4.0 gpm (15 L/m) total flow, where one outlet is the hand shower.
L 402.6.2 Bath and Shower Diverters
The rate of leakage out of the tub spout of bath and shower diverters while operating in the shower mode shall not exceed 0.1 gpm (0.4 L/m) in accordance with ASME A112.18.1/CSA B125.1.
L 402.6.3 Shower Valves
Shower valves shall comply with the temperature control performance requirements of ASSE 1016 or ASME A112.18.1/CSA B125.1 where tested at 2.0 gpm (7.6 L/m).
Upcodes Diagrams
Related Code Sections
L 402.6 Sustainable Practices, Showerheads
Showerheads shall not exceed 2.0 gpm (7.6 L/m) at 80 psi (552 kPa), and shall be listed to ASME A112.18.1/CSA B125.1 and the EPA WaterSense ...
408.9 Plumbing Fixtures and Fixture Fittings, Location of Valves and Heads
Control valves and showerheads shall be located on the sidewall of shower compartments or otherwise arranged so that the showerhead does ...
Section P2710 Plumbing Fixtures, Shower Walls
Walls in shower compartments and walls above bathtubs that have a wall-mounted showerhead shall be finished in accordance with Section R307.2 ...
408.2 Plumbing Fixtures and Fixture Fittings, Water Consumption
Showerheads shall have a maximum flow rate of not more than 2.5 gpm at 80 psi (9.5 L/m at 552 kPa) ...
408.3 Plumbing Fixtures and Fixture Fittings, Individual Shower and Tub-Shower Combination Control Valves
balance/thermostatic mixing valve type that provide scald and thermal shock protection for the rated flow rate of the installed showerhead. These ...