// CODE SNIPPET
421.5 Shower Floors or Receptors
Go To Full Code Chapter
Floor surfaces shall be constructed of impervious, noncorrosive, nonabsorbent and waterproof materials.
421.5.1 Support
Floors or receptors under shower compartments shall be laid on, and supported by, a smooth and structurally sound base.
421.5.2 Shower Lining
Floors under shower compartments, except where prefabricated receptors have been provided, shall be lined and made watertight utilizing material complying with Sections 421.5.2.1 through 421.5.2.6. Such liners shall turn up on all sides not less than 2 inches (51 mm) above the finished threshold level. Liners shall be recessed and fastened to an approved backing so as not to occupy the space required for wall covering, and shall not be nailed or perforated at any point less than 1 inch (25 mm) above the finished threshold. Liners shall be pitched one-fourth unit vertical in 12 units horizontal (2-percent slope) and shall be sloped toward the fixture drains and be securely fastened to the waste outlet at the seepage entrance, making a watertight joint between the liner and the outlet. The completed liner shall be tested in accordance with Section 312.9.
Exceptions:
- Floor surfaces under shower heads provided for rinsing laid directly on the ground are not required to comply with this section.
- Where a sheet-applied, load-bearing, bonded, waterproof membrane is installed as the shower lining, the membrane shall not be required to be recessed.
421.5.2.1 PVC Sheets
Plasticized polyvinyl chloride (PVC) sheets shall meet the requirements of ASTM D4551. Sheets shall be joined by solvent welding in accordance with the manufacturer's installation instructions.
421.5.2.2 Chlorinated Polyethylene (CPE) Sheets
Nonplasticized chlorinated polyethylene sheet shall meet the requirements of ASTM D4068. The liner shall be joined in accordance with the manufacturer's installation instructions.
421.5.2.3 Sheet Lead
Sheet lead shall weigh not less than 4 pounds per square foot (19.5 kg/m2) and shall be coated with an asphalt paint or other approved coating. The lead sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or an equivalent. Sheet lead shall be joined by burning.
421.5.2.4 Sheet Copper
Sheet copper shall conform to ASTM B152 and shall weigh not less than 12 ounces per square foot (3.7 kg/m2). The copper sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or an equivalent. Sheet copper shall be joined by brazing or soldering.
421.5.2.5 Sheet-Applied, Load-Bearing, Bonded, Waterproof Membranes
Sheet-applied, load-bearing, bonded, waterproof membranes shall meet the requirements of ANSI A118.10 and shall be applied in accordance with the manufacturer's installation instructions.
421.5.2.6 Liquid-Type, Trowel-Applied, Load-Bearing, Bonded Waterproof Materials
Liquid-type, trowel-applied, load-bearing, bonded waterproof materials shall meet the requirements of ANSI A118.10 and shall be applied in accordance with the manufacturer's instructions.
Upcodes Diagrams
Related Code Sections
417.5 Fixtures, Faucets and Fixture Fittings, Shower Floors or Receptors
Floors or receptors under shower compartments shall be laid on, and supported by, a smooth ...
417.5 Fixtures, Faucets and Fixture Fittings, Shower Floors or Receptors
Floors or receptors under shower compartments shall be laid on, and supported by, a smooth ...
421.5 Fixtures, Faucets and Fixture Fittings, Shower Floors or Receptors
Floors or receptors under shower compartments shall be laid on, and supported by, a smooth ...
417.5.2.2 Fixtures, Faucets and Fixture Fittings, Chlorinated Polyethylene (CPE) Sheets
Nonplasticized chlorinated polyethylene sheet shall be a minimum 0.040 inch (1.02 mm) thick, and shall meet the requirements of ASTM D 4068. The liner ...
417.5.2.2 Fixtures, Faucets and Fixture Fittings, Chlorinated Polyethylene (CPE) Sheets
Nonplasticized chlorinated polyethylene sheet shall meet the requirements of ASTM D 4068. The liner shall be joined in accordance ...