431.1 General
In all groups other than Group E, short-term holding areas shall be permitted to be classified as the main occupancy, provided all of the following are met:
  1. Provisions are made for the release of all restrained or detained occupants of short-term holding areas at all times.
  2. Aggregate area of short-term holding areas shall not occupy more than 10 percent of the building area of the story in which they are located and shall not exceed the tabular values for building area in Table 506.2 without building area increases.
  3. Restrained or detained occupant load of each shortterm holding area shall not exceed 20.
  4. Aggregate restrained or detained occupant load in short-term holding areas per building shall not exceed 80.
  5. Compliance with Sections 408.3.7, 408.3.8, 408.4, and 408.7 as applicable for Group I-3 occupancies.
  6. Requirements of the main occupancy in which shortterm holding areas are located shall be met.
  7. Fire areas containing short-term holding areas shall be provided with a fire alarm system and automatic smoke detection system complying with Section 907.2.6.3 as applicable to I-3 occupancies.
  8. Where each fire area containing short-term holding areas exceeds 12,000 square feet (1115 m2), such fire areas shall be provided with an automatic sprinkler system complying with Section 903.3.
  9. Short-term holding areas shall be separated from other short-term holding areas and adjacent spaces by smoke partitions complying with Section 710.
Upcodes Diagrams

Related Code Sections

Section 427 Special Detailed Requirements Based on Use and Occupancy, Short-Term Holding Areas
In all groups other than Group E, short-term holding areas shall be permitted to be classified as the main occupancy, provided all of the following ...
Section 431 Special Detailed Requirements Based on Use and Occupancy, Short-Term Holding Areas
In all groups other than Group E, short-term holding areas shall be permitted to be classified as the main occupancy, provided all of the following ...
Section 429 Special Detailed Requirements Based on Use and Occupancy, Short-Term Holding Areas
In all groups other than Group E, short-term holding areas shall be permitted to be classified as the main occupancy, provided all of the following ...