2412.5.1
Shelf angles shall be of corrosion resistant material capable of supporting four times the width of the supported veneer. The shelf angles shall be spaced vertically in alternate horizontal joints, but not more than 3 feet (914 mm) apart. Shelf angles shall be secured to the wall at intervals not exceeding 2 feet (610 mm) with corrosion-resistant bolts not less than 1/4 inch (6.4 mm) diameter. Bolts shall be set in masonry and secured by lead shields.
2412.5.2
Ties shall be of corrosion-resistant metal as manufactured especially for holding glass-veneer sheets to masonry surfaces. There shall be not less than one such approved tie for each 2 square feet (0.19 m2) of veneer surface.

Related Code Sections

2412.5 Glass and Glazing, Shelf Angles and Ties
Shelf angles shall be of corrosion-resistant material capable of supporting four times the width of the supported veneer. The shelf angles shall ...
2412.5 Glass and Glazing, Shelf Angles and Ties
Shelf angles shall be of corrosion resistant material capable of supporting four times the width of the supported veneer. The shelf angles shall ...
2412.5 Glass and Glazing, Shelf Angles and Ties
Shelf angles shall be of corrosion resistant material capable of supporting four times the width of the supported veneer. The shelf angles shall ...
2412.5.2 Glass and Glazing,
Ties shall be of corrosion-resistant metal as manufactured especially for holding glass-veneer sheets to masonry surfaces. There shall be not less ...
2412.3.1 Glass and Glazing,
Where more than 6 feet (1829 mm) above grade, veneer shall be supported by shelf angles, and ties shall be used in both horizontal and vertical ...