2106.5.2 Shear Wall Shear Strength
Go To Full Code Chapter
For a shear wall whose nominal shear strength exceeds the shear corresponding to development of its nominal flexural strength, two shear regions exist.
For all cross sections within a region defined by the base of the shear wall and a plane at a distance Lw above the base of the shear wall, the nominal shear strength shall be determined by Equation 21-1.
Vn = An ρn fy
(Equation 21-1)
The required shear strength for this region shall be calculated at a distance Lw/2 above the base of the shear wall, but not to exceed one-half story height. For the other region, the nominal shear strength of the shear wall shall be determined from Section 2108.
Upcodes Diagrams
Related Code Sections
2106.5.2 Masonry, Shear Wall Shear Strength
For a shear wall whose nominal shear strength exceeds the shear corresponding to development of its nominal flexural strength, two shear regions ...
2305.1.1 Wood, Shear Resistance Based on Principles of Mechanics
Shear resistance of diaphragms and shear walls are permitted to be calculated by principles of mechanics using values of fastener strength ...
17.2.3.5.2 Anchoring to Concrete,
steel track of bearing or nonbearing walls of light-frame construction to foundations or foundation stem walls, the in-plane shear strength in accordance ...
1908.1.6 Concrete, ACI 318, Section 17.2.3
the calculation of the in-plane shear strength of anchor bolts attaching wood sill plates of bearing or nonbearing walls of light-frame wood structures ...
1908.1.9 Concrete, ACI 318, Section D.3.3
of bearing or nonbearing walls of light-frame wood structures to foundations or foundation stem walls, the in-plane shear strength in accordance ...