// CODE SNIPPET
G.2.2.1 Shaft Requirements
Go To Full Code Chapter
Vertical runs of high pressure gas piping within a building shall be enclosed in masonry shafts constructed of walls not less than 4 inches (101.6 mm) in thickness and sealed to prevent any gas leakage from the shaft. Such shaft shall be vented to the outdoors at the top. Such shaft shall not be located adjacent to an exit stairway or exit passageway unless the shaft wall separating the exit stairway or exit passageway from the shaft is designed to resist a potential gas explosion in accordance with Section 1615.6 of the New York City Building Code.
Upcodes Diagrams
Related Code Sections
G.2.2.1 High Pressure Natural Gas Installations, Shaft Requirements
Vertical runs of high pressure gas piping within a building shall be enclosed in masonry shafts constructed of walls not less than 4 inches (101.6 mm ...
G.2.2.1 High Pressure Natural Gas Installations, Shaft Requirements
Vertical runs of high pressure gas piping within a building shall be enclosed in masonry shafts constructed of walls not less than 4 inches (100 mm ...
707.2 Fire-Resistance-Rated Construction, Shaft Enclosure Required
: 1. A shaft enclosure is not required for openings totally within an individual residential dwelling unit and connecting four stories or less where ...
708.2 Fire and Smoke Protection Features, Shaft Enclosure Required
is fully sprinklered in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
A shaft enclosure is not required in a building equipped ...
713.1 Fire and Smoke Protection Features, General
The provisions of this section shall apply to shafts required to protect openings and
penetrations through floor/ceiling and roof/ceiling assemblies ...