Drainage piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table P3113.4.1.
TABLE P3113.4.1
SIZE AND LENGTH OF SUMP VENTS
DISCHARGE CAPACITY OF PUMP (gpm) MAXIMUM DEVELOPED LENGTH OF VENT (feet)a
Diameter of vent (inches)
11/4 11/2 2 21/2 3
10
No limitb No limit No limit No limit No limit
20
270 No limit No limit No limit No limit
40
72 160 No limit No limit No limit
60
31 75 270 No limit No limit
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute (gpm) = 3.785 L/m.
  1. Developed length plus an appropriate allowance for entrance losses and friction caused by fittings, changes in direction and diameter. Suggested allowances shall be obtained from NBS Monograph 31 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.
  2. Actual values greater than 500 feet.
Upcodes Diagrams

Related Code Sections

906.5.1 Vents, Sewage Pumps and Sewage Ejectors Other Than Pneumatic
pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 906.5.1. TABLE 906.5.1 SIZE AND LENGTH OF SUMP VENTS ...
P3113.4.1 Vents, Sewage Pumps and Sewage Ejectors Other Than Pneumatic
pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table P3113.4.1. TABLE P3113.4.1 SIZE AND LENGTH OF SUMP ...
P3113.4.1 Vents, Sewage Pumps and Sewage Ejectors Other Than Pneumatic
pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table P3113.4.1. TABLE P3113.4.1 SIZE AND LENGTH OF SUMP VENTS ...
Section 906 Vents, Vent Pipe Sizing
in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall ...
906.5.2 Vents, Pneumatic Sewage Ejectors
The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent ...