A sewage ejector, sewage pump, or grinder pump receiving discharge from a water closet shall have minimum discharge velocity of 1.9 feet per second (0.579 m/s) throughout the discharge piping to the point of connection with a gravity building drain, gravity sewer or pressure sewer system. A nongrinding pump or ejector shall be capable of passing a 11/2-inch-diameter (38 mm) solid ball, and the discharge piping shall be not less than 2 inches (51 mm) in diameter. The discharge piping of grinding pumps shall be not less than 11/4 inches (32 mm) in diameter. A check valve and a gate valve located on the discharge side of the check valve shall be installed in the pump or ejector discharge piping between the pump or ejector and the drainage system. Access shall be provided to such valves. Such valves shall be located above the sump cover or, where the discharge pipe from the ejector is below grade, the valves shall be accessibly located outside the sump below grade in an access pit with a removeable access cover.
Exception: Macerating toilet systems shall be permitted to have the discharge pipe sized in accordance with manufacturer's instructions, but not less than 0.75 inch (19 mm) in diameter.
Upcodes Diagrams

Related Code Sections

P3007.1 Sanitary Drainage, Sewage Ejectors or Sewage Pumps
A sewage ejector, sewage pump, or grinder pump receiving discharge from a water closet shall have minimum discharge velocity of 1.9 feet per second ...
712.4 Sanitary Drainage, Sewage Pumps and Sewage Ejectors
A sewage pump or sewage ejector shall automatically discharge the contents of the sump to the building drainage system ...
712.4 Sanitary Drainage, Sewage Pumps and Sewage Ejectors
A sewage pump or sewage ejector shall automatically discharge the contents of the sump to the building drainage system ...
712.4 Sanitary Drainage, Sewage Pumps and Sewage Ejectors
A sewage pump or sewage ejector shall automatically discharge the contents of the sump to the building drainage system ...
712.4.1 Sanitary Drainage, Macerating Toilet Systems
Macerating toilet systems shall comply with ASME A112.3.4/CSA B45.9 and shall be installed in accordance with the manufacturer's instructions ...