A sewage ejector or sewage pump receiving the discharge of water closets or urinals:
  1. Shall have a discharge capacity of not less than 20 gpm (1.26 L/s).
  2. In single dwelling units, the ejector or pump shall be capable of passing an 11/2 inch (38 mm) diameter solid ball, and the discharge piping of each ejector or pump shall have a backwater valve and gate valve, and be not less than 2 inches (50 mm) in diameter.
  3. In other than single-dwelling units, the ejector or pump shall be capable of passing a 2 inch (51 mm) diameter solid ball, and the discharge piping of each ejector or pump shall have a backwater valve and gate valve, and be not less than 3 inches (80 mm) in diameter.

Related Code Sections

710.3 Sanitary Drainage, Sewage Ejector and Pumps
A sewage ejector or sewage pump receiving the discharge of water closets or urinals: Shall have a discharge capacity of not less than 20 gpm (1.26 ...
P3007.4 Sanitary Drainage, Sewage Pumps and Sewage Ejectors
A sewage pump or sewage ejector shall automatically discharge the contents of the sump to the building drainage system ...
P3113.4.1 Vents, Sewage Pumps and Sewage Ejectors Other Than Pneumatic
pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table P3113.4.1. TABLE P3113.4.1 SIZE AND LENGTH OF SUMP VENTS ...
Section P3113 Vents, Vent Pipe Sizing
piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps ...
P3113.4.2 Vents, Pneumatic Sewage Ejectors
The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent ...