6.4.3.2 Setpoint Overlap Restriction
Go To Full Code Chapter
Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches; mechanical stops; or, for DDC systems, software programming) shall be provided to prevent the heating setpoint from exceeding the cooling setpoint minus any applicable proportional band.
Upcodes Diagrams
Related Code Sections
6.4.3.2 Heating, Ventilating, and Air Conditioning, Setpoint Overlap Restriction
; mechanical stops; or, for DDC systems, software programming) shall be provided to prevent the heating setpoint from exceeding the cooling setpoint minus ...
C403.2.4.1.3 [CE] Commercial Energy Efficiency, Setpoint Overlap Restriction
Where a zone has a separate heating and a separate cooling thermostatic control located within the zone , a limit switch, mechanical stop or direct ...
C403.4.1.3 [CE] Commercial Energy Efficiency, Setpoint Overlap Restriction
digital control system with software programming shall be configured to prevent the heating setpoint from exceeding the cooling setpoint and to maintain ...
503.2.4.2 Commercial Energy Efficiency, Set Point Overlap Restriction
Where used to control both heating and cooling, zone thermostatic controls shall provide a temperature range or deadband of at least 5°F (2.8°C ...
6.4.3.2 Heating, Ventilating, and Air Conditioning, Set-Point Overlap Restriction
Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches ...