6.4.3.3.2 Setback Controls
Go To Full Code Chapter
Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating set point at least 10°F below the occupied heating set point. Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system as required to maintain zone temperatures below an adjustable cooling set point at least 5°F above the occupied cooling set point or to prevent high space humidity levels.
Upcodes Diagrams
Related Code Sections
6.4.3.3.2 Heating, Ventilating, and Air Conditioning, Setback Controls
Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required ...
N1103.2 [RE] Energy Efficiency, (R403.2) Hot Water Boiler Outdoor Temperature Setback
Hot water boilers that supply heat to the building through one- or two-pipe heating systems shall have an outdoor setback control that decreases ...
6.5.3.4 Heating, Ventilating, and Air Conditioning, Parallel-Flow Fan-Powered VAV Air Terminal Control
heating for warm-up or setback temperature control, either operate the terminal fan and heating coil without primary air or reverse the terminal ...
1105.2 Storm Drainage, Setback Roofs
Drains on setback roofs shall be permitted to be connected to the controlled-flow drainage systems provided:
The setback is designed for storing ...
R324.6.2 Building Planning, Setback at Ridge
For photovoltaic arrays occupying not more than 33 percent of the plan view total roof area, not less than an 18-inch (457 mm) clear setback ...