7.4.4.1 Temperature Controls
Temperature controls shall be provided that allow for storage temperature adjustment from 120°F or lower to a maximum temperature compatible with the intended use.
Exception to 7.4.4.1
When the manufacturers' installation instructions specify a higher minimum thermostat setting to minimize condensation and resulting corrosion.
7.4.4.2 Temperature Maintenance Controls
Systems designed to maintain usage temperatures in hot-water pipes, such as recirculating hot-water systems or heat trace, shall be equipped with automatic time switches or other controls that can be set to switch off the usage temperature maintenance system during extended periods when hot water is not required.
7.4.4.3 Outlet Temperature Controls
Temperature controlling means shall be provided to limit the maximum temperature of water delivered from lavatory faucets in public facility restrooms to 110°F.
7.4.4.4 Circulating Pump Controls
When used to maintain storage tank water temperature, recirculating pumps shall be equipped with controls limiting operation to a period from the start of the heating cycle to a maximum of five minutes after the end of the heating cycle.
Upcodes Diagrams

Related Code Sections

7.4.4 Service Water Heating, Service Water-Heating System Controls
designed to maintain usage temperatures in hot-water pipes, such as recirculating hot-water systems or heat trace, shall be equipped with automatic time ...
7.9 Service Water Heating, Verification, Testing, and Commissioning
that systems and controls are configured and operating in accordance with applicable requirements of service water heating system temperature controls ...
N1101.5 [RE] Energy Efficiency, (R103.2) Information on Construction Documents
heat gain coefficient (SHGC) calculations. Mechanical system design criteria. Mechanical and service water heating systems and equipment types, sizes ...
L 503.3 Sustainable Practices, Mandatory Provisions
Service water heating system controls shall comply with Section L 503.3.5(1) and Section L 503.3.5(2). Temperature controls shall be provided ...