// CODE SNIPPET
E3602.2 Service Load
Go To Full Code Chapter
TABLE E3602.2 [220.82(B) & (C)]
MINIMUM SERVICE LOAD CALCULATION
The minimum load for ungrounded service conductors and service devices that serve 100 percent of the dwelling unit load shall be computed in accordance with Table E3602.2. Ungrounded service conductors and service devices that serve less than 100 percent of the dwelling unit load shall be computed as required for feeders in accordance with Chapter 37. [220.82(A)]
TABLE E3602.2 [220.82(B) & (C)]
LOADS AND PROCEDURE |
3 volt-amperes per square foot of floor area for general lighting and general use receptacle outlets. |
Plus |
1,500 volt-amperes multiplied by total number of 20-ampere-rated small appliance and laundry circuits. |
Plus |
The nameplate volt-ampere rating of all fastened-in-place, permanently connected or dedicated circuit-supplied appliances such as ranges, ovens, cooking units, clothes dryers not connected to the laundry branch circuit and water heaters. |
Apply the following demand factors to the above subtotal: |
The minimum subtotal for the loads above shall be 100 percent of the first 10,000 volt-amperes of the sum of the above loads plus 40 percent of any portion of the sum that is in excess of 10,000 volt-amperes. |
Plus the largest of the following: |
One hundred percent of the nameplate rating(s) of the air-conditioning and cooling equipment. |
One hundred percent of the nameplate rating(s) of the heat pump where a heat pump is used without any supplemental electric heating. |
One hundred percent of the nameplate rating of the electric thermal storage and other heating systems where the usual load is expected to be continuous at the full nameplate value. Systems qualifying under this selection shall not be figured under any other category in this table. |
One hundred percent of nameplate rating of the heat pump compressor and 65 percent of the supplemental electric heating load for central electric space-heating systems. If the heat pump compressor is prevented from operating at the same time as the supplementary heat, the compressor load does not need to be added to the supplementary heat load for the total central electric space-heating load. |
Sixty-five percent of nameplate rating(s) of electric space-heating units if less than four separately controlled units. |
Forty percent of nameplate rating(s) of electric space-heating units of four or more separately controlled units. |
The minimum total load in amperes shall be the volt-ampere sum calculated above divided by 240 volts. |
E3602.2.1 Services Under 100 Amperes
Services that are not required to be 100 amperes shall be sized in accordance with Chapter 37. [230.42(A), (B), and (C)].
Related Code Sections
E3602.2 Services, Service Load
The minimum load for ungrounded service conductors and service devices that serve 100 percent of the dwelling unit load shall be computed ...
(A) Wiring and Protection, Feeder and Service Load
This section applies to a dwelling unit having the total connected load served by a single 120/240-volt or 208Y/120-volt set of 3-wire service ...
6.6.3.2 Structural Analysis, Service Load Analysis
Immediate and time-dependent deflections due to gravity loads shall be calculated in accordance with 24.2 ...
6.6.3.2 Structural Analysis, Service Load Analysis
Immediate and time-dependent deflections due to gravity loads shall be calculated in accordance with 24.2 ...
6.7.2.2 Structural Analysis, Service Load Analysis
Immediate and time-dependent deflections due to gravity loads shall be calculated in accordance with 24.2 ...