603.2 Separation of Water Service and Building Sewer
JUMP TO FULL CODE CHAPTER
Water service pipe and the building sewer shall be separated by not less than 5 feet (1524 mm) of undisturbed or compacted earth.
Exceptions:
- The required separation distance shall not apply where the bottom of the water service pipe within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conform to Table 702.3.
- Water service pipe is permitted to be located in the same trench with a building sewer, provided such sewer is constructed of materials listed in Table 702.2.
- The required separation distance shall not apply where a water service pipe crosses a sewer pipe, provided the water service pipe is sleeved to a point not less than 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing with pipe materials listed in Table 605.3, 702.2 or 702.3.
Potable water service pipes shall not be located in, under or above cesspools, septic tanks, septic tank drainage fields or seepage pits (see Section 605.1 for soil and groundwater conditions).
Related Code Sections
603.2 Water Supply and Distribution, Separation of Water Service and Building Sewer
Where water service piping is located in the same trench with the building sewer , such sewer shall be constructed of materials listed in Table ...
2017 FBC - Plumbing, 6th edition > 6 Water Supply and Distribution > 603 Water Service > 603.2 Separation of Water Service and Building Sewer
603.2 Water Supply and Distribution, Separation of Water Service and Building Sewer
Where water service piping is located in the same trench with the building sewer , such sewer shall be constructed of materials listed in Table ...
2020 FBC - Plumbing, 7th edition > 6 Water Supply and Distribution > 603 Water Service > 603.2 Separation of Water Service and Building Sewer
603.2 Water Supply and Distribution, Separation of Water Service and Building Sewer
Water service pipe and the building sewer shall be separated by not less than 5 feet (1524 mm) of undisturbed or compacted earth. Exceptions ...
2014 FBC - Plumbing, 5th edition > 6 Water Supply and Distribution > 603 Water Service > 603.2 Separation of Water Service and Building Sewer
P2906.4.1 Water Supply and Distribution, Separation of Water Service and Building Sewer
of materials indicated in Table P3002.1(2), the water service pipe and the building sewer shall be horizontally separated by not less than 5 feet (1524 mm ...
2017 FBC - Residential, 6th edition > 29 Water Supply and Distribution > P2906 Materials, Joints and Connections > P2906.4 Water Service Pipe > P2906.4.1 Separation of Water Service and Building Sewer
P2906.4.1 Water Supply and Distribution, Separation of Water Service and Building Sewer
of materials indicated in Table P3002.1(2), the water service pipe and the building sewer shall be horizontally separated by not less than 5 feet (1524 mm ...
2020 FBC - Residential, 7th edition > 29 Water Supply and Distribution > P2906 Materials, Joints and Connections > P2906.4 Water Service Pipe > P2906.4.1 Separation of Water Service and Building Sewer