UpCodes logo
Jump To Full Code Chapter
Separation of Level 2 and 3 aerosol product areas or plastic aerosol 3 product areas shall comply with the following:
  1. Level 2 and 3 aerosol product or plastic aerosol 3 product display and merchandising areas shall be separated from each other by not less than 25 feet (7620 mm). See Table 5106.2.1.
  2. Level 2 and 3 aerosol product or plastic aerosol 3 product display and merchandising areas shall be separated from flammable and combustible liquids storage and display areas by one or a combination of the following:
    2.1. Segregating areas from each other by horizontal distance of not less than 25 feet (7620 mm).
    2.2. Isolating areas from each other by a noncombustible partition extending not less than 18 inches (457 mm) above the merchandise.
    2.3. In accordance with Section 5106.5.
  3. Where Item 2.2 is used to separate Level 2 or 3 aerosol products or plastic aerosol 3 products from flammable or combustible liquids, and the aerosol products are located within 25 feet (7620 mm) of flammable or combustible liquids, the area below the noncombustible partition shall be liquid tight at the floor to prevent spilled liquids from flowing beneath the aerosol products.

Related Code Sections

5104.7 Aerosols, Storage in Group M Occupancies
Storage of Level 2 and 3 aerosol productsaerosol cooking spray products and plastic aerosol 3 products in occupancies in Group M ...
5104.3.2 Aerosols, Segregated Storage
Storage of Level 2 and 3 aerosol products segregated into areas utilized exclusively for the storage of aerosol products shall comply with Table ...
Section 5106 Aerosols, Retail Display
Separation of Level 2 and 3 aerosol product areas shall comply with the following: Level 2 and 3 aerosol product display and merchandising ...
Section 5105 Aerosols, Outside Storage
The outside storage of Level 2 and 3 aerosol products and plastic aerosol 3 products, including storage in temporary storage trailers, shall ...