453.4.1 Separation of Laboratory Suites
Go To Full Code Chapter
453.4.1.1
Laboratory suites shall be separated from other occupancies in accordance with Table 508.4.
453.4.1.2
Laboratory suites shall be separated from other laboratory suites by a fire barrier having a fire-resistance rating of not less than 1-hour.
453.4.1.3
Laboratory suites shall be separated from control areas by a minimum 2-hour fire-resistance rating in accordance with Sections 707 and 711.
Exception: Laboratory suites shall be separated from control areas by a minimum 1-hour fire-resistance rating on floor levels below the 4th story.
453.4.1.4 Horizontal Separation
The floor construction of the laboratory suite and the construction supporting the floor of the laboratory suite shall have a minimum 2-hour fire-resistance rating in accordance with Section 711.
Exceptions:
- The floor construction of the laboratory suite and the construction supporting the floor of the laboratory suite are allowed to be 1-hour fire-resistance rated in buildings of Type IIA, IIIA and VA construction.
- When an individual laboratory suite occupies more than one story, the intermediate floors contained within the suite shall comply with the requirements of Table 601.
Upcodes Diagrams
Related Code Sections
453.4.1 Special Detailed Requirements Based on Use and Occupancy, Separation of Laboratory Suites
Laboratory suites shall be separated from other occupancies in accordance with Table 508.4 ...
453.4.1 Special Detailed Requirements Based on Occupancy and Use, Separation of Laboratory Suites
Laboratory suites shall be separated from other occupancies in accordance with Table 508.4 ...
453.4.1 Special Detailed Requirements Based on Occupancy and Use, Separation of Laboratory Suites
Laboratory suites shall be separated from
other occupancies in accordance with Table 508.4 ...
453.4.1.3 Special Detailed Requirements Based on Occupancy and Use,
Laboratory suites shall be separated from control areas by a minimum 2-hour fire-resistance rating in accordance with Sections 707 and 711 ...
453.4.1.1 Special Detailed Requirements Based on Use and Occupancy,
Laboratory suites shall be separated from other occupancies in accordance with Table 508.4 ...