High-piled storage areas shall be separated from other portions of the building where required by Sections 3206.3.1 through 3206.3.2.2.
3206.3.1 Separation From Other Uses
Mixed occupancies shall be separated in accordance with the International Building Code.
3206.3.2 Multiple High-Piled Storage Areas
Multiple high-piled storage areas shall be in accordance with Section 3206.3.2.1 or 3206.3.2.2.
3206.3.2.1 Aggregate Area
The aggregate of all high-piled storage areas within a building shall be used for the application of Table 3206.2 unless such areas are separated from each other by 1-hour fire barriers constructed in accordance with Section 707 the International Building Code. Openings in such fire barriers shall be protected by opening protectives having a 1-hour fire protection rating.
3206.3.2.2 Multiclass High-Piled Storage Areas
High-piled storage areas classified as Class I through IV not separated from high-piled storage areas classified as high hazard shall utilize the aggregate of all high-piled storage areas as high hazard for the purposes of the application of Table 3206.2. To be considered as separated, 1-hour fire barriers shall be constructed in accordance with Section 707 of the International Building Code. Openings in such fire barriers shall be protected by opening protectives having a 1-hour fire protection rating.

Exception: As provided for in Section 3204.2.