UpCodes logo
Go To Full Code Chapter
A sheet or liquid-applied Class II vapor retarder shall be installed between bales and supporting concrete or masonry. The bales shall be separated from the vapor retarder by not less than 3/4 inch (19.1 mm), and that space shall be filled with an insulating material such as wood or rigid insulation, or a material that allows vapor dispersion such as gravel, or other approved insulating or vapor dispersion material. Sill plates shall be installed at this interface in accordance with Section AS105.3. Where bales abut a concrete or masonry wall that retains earth, a Class II vapor retarder shall be provided between such wall and the bales.
Upcodes Diagrams

Related Code Sections

AS105.6.5 Strawbale Construction, Separation of Bales and Concrete
A sheet or liquid-applied Class II vapor retarder shall be installed between bales and supporting concrete or masonry. The bales shall be separated ...
AS105.6.5 Strawbale Construction, Separation of Bales and Concrete
A sheet or liquid-applied Class II vapor retarder shall be installed between bales and supporting concrete or masonry. The bales shall be separated ...
AS105.6.5 Strawbale Construction, Separation of Bales and Concrete
A sheet or liquid-applied Class II vapor retarder shall be installed between bales and supporting concrete or masonry. The bales shall be separated ...
Section AS103 Strawbale Construction, Bales
Bales shall be rectangular in shape, except for partial bales made to fill nonrectangular spaces in accordance with Section AS103.6 ...