Generation, compression and dispensing equipment shall be separated from other fuels or equivalent risks to life, safety and buildings or public areas in accordance with Table 2209.3.1.
Exception: Closed systems with a hydrogen capacity of 3,000 cubic feet (85 m3) or less at NTP.
TABLE 2209.3.1
MINIMUM SEPARATION FOR GASEOUS HYDROGEN DISPENSERS, COMPRESSORS, GENERATORS AND STORAGE VESSELS
OUTDOOR EQUIPMENT OR FEATURE DISTANCEa (feet)
Building—Noncombustible walls 10b, c
Building—Combustible walls 25b, c
Public sidewalks and parked vehicles 15b, c
Lot line 10b
Air intake openings 25d
Wall openings located less than 25 feet above grade 20d
Wall openings located 25 feet or more above grade 25d
Outdoor public assembly 25b
Ignition sourcee 10
Above-ground flammable or combustible liquid storage—diked in accordance with Section 3404.2.9.7, distance to dike wall 20
Above-ground flammable or combustible liquid storage—not diked in accordance with Section 3404.2.9.7, distance to tank 50
Underground flammable or combustible liquid storage—distance to vent or fill opening 20
Flammable gas storage (other than hydrogen)— with emergency shutoff interconnected with the hydrogen system 25
Above-ground flammable gas storage (other than hydrogen)—without emergency shutoff interconnected with the hydrogen system 50
Combustible waste material (see Section 304.1.1) 50b
Vertical plane of the nearest overhead electric wire of an electric trolley, train or bus line 50
Vertical plane of the nearest wire of overhead electrical power distribution lines 5
For SI: 1 foot = 304.8 mm. 1 cubic foot = 0.02832 m3.
  1. The applicability of tabular distance is in terms of a radius that defines a hemisphere from the source when not interrupted by an intervening fire barrier without through penetrations.
  2. See Section 2209.3.1.1.
  3. The dispenser and point of transfer for dispensing need not be separated from canopies constructed in accordance with Section 406.5 of the International Building Code and constructed in a manner that prevents the accumulation of hydrogen gas.
  4. Measured along the natural and unobstructed line of travel (e.g., around protective walls, around corners of buildings).
  5. Ignition sources include appliance burner igniters, hot work and hot surfaces capable of igniting flammable vapors.
2209.3.1.1 Barrier Wall Construction—Gaseous Hydrogen
The outdoor separation shall be allowed to be reduced to 5 feet (1524 mm) where a 2-hour fire barrier interrupts the line of sight between equipment, other than dispensers, and the exposure within the radial distance as indicated by the tabular value. The height of the barrier shall be a minimum of 6 feet (1829 mm), but not less than 1.5 times the height of the equipment, measured vertically. The length of the wall shall be not less than 1.5 times the maximum diameter or length of the tank.
2209.3.1.2 Location of Equipment
Equipment shall be located from the enclosing walls at a distance not less than one tank diameter. When horizontal tanks are used, the distance from any one enclosing wall shall be not less than one-half the length of the tank or a minimum of 5 feet (1524 mm).
Upcodes Diagrams

Related Code Sections

63.4.6 Compressed Gases and Cryogenic Fluids, Separation From Hazardous Conditions
containers located outdoors shall be separated from exposure hazards in accordance with the minimum separation distances indicated in Table 63.4.6.2 ...
63.4.7 Compressed Gases and Cryogenic Fluids, Separation From Hazardous Conditions
containers located outdoors shall be separated from exposure hazards in accordance with the minimum separation distances indicated in Table 63.4.7.2 ...
Section 3204 Cryogenic Fluids, Storage
Cryogenic containers and systems in outdoor storage shall be separated from materials and conditions that pose exposure hazards ...