66.9.16 Separation From Incompatible Materials
Go To Full Code Chapter
66.9.16.1
Except as provided for in 66.9.16.3, ignitible (flammable or combustible) liquids shall be separated from incompatible materials where the stored materials are in containers having a capacity of more than 5 lb (2.268 kg) or 1/2 gal (1.89 L). [30:9.17.1]
66.9.16.1.1
Separation shall be accomplished by one of the following methods:
- Segregating incompatible materials storage by a distance of not less than 20 ft (6.1 m)
- Isolating incompatible materials storage by a noncombustible partition extending not less than 18 in. (460 mm) above and to the sides of the stored materials
- Storing liquid materials in Class I liquids [FP < 100°F (37.8°C)] storage cabinets in accordance with 66.9.4
66.9.16.2
Ignitible (flammable or combustible) liquids shall
be separated from Level 2 and Level 3 aerosols in accordance
with Chapter 61 and NFPA 30B. [30:9.17.2]
66.9.16.4
Materials that are water-reactive, as described in
NFPA 704 shall not be stored in the same control area with
ignitible (flammable or combustible) liquids. [30:9.17.4]
Upcodes Diagrams
Related Code Sections
66.9.16 Flammable and Combustible Liquids, Separation From Incompatible Materials
Except as provided for in 66.9.16.3, ignitible (flammable or combustible) liquids shall be separated from incompatible materials where the stored ...
66.9.17 Flammable and Combustible Liquids, Separation From Incompatible Materials
Except as provided for in 66.9.17.3, liquids shall be separated from incompatible materials where the stored materials are in containers having ...
66.9.16.1 Flammable and Combustible Liquids,
Except as provided for in 66.9.16.3, ignitible (flammable or combustible) liquids shall be separated from incompatible materials where the stored ...
66.9.16.1.1 Flammable and Combustible Liquids,
Separation shall be accomplished by one of the following methods:
Segregating incompatible materials storage by a distance of not less than 20 ...
66.9.16.3 Flammable and Combustible Liquids,
Liquids shall be separated from oxidizers by at least
25 ft (7.6 m). [30:9.17.3] ...