(A) Separate Branches
Go To Full Code Chapter
Type 1 essential electrical systems shall be comprised of three separate branches capable of supplying a limited amount of lighting and power service that is considered essential for life safety and effective hospital operation during the time the normal electrical service is interrupted for any reason. The three branches are life safety, critical, and equipment.
The division between the branches shall occur at transfer switches where more than one transfer switch is required. [99:6.7.2.3.1]
Related Code Sections
(A) Special Occupancies, Separate Branches
Essential electrical systems for hospitals shall be comprised of three separate branches capable of supplying a limited amount of lighting and power ...
(A) Special Occupancies, Separate Branches
Type 1 essential electrical systems shall be comprised of three separate branches capable of supplying a limited amount of lighting and power service ...
(A) Special Equipment, Separate Branch Circuits
The branch circuit(s) supplying the lighting for machine rooms, control rooms, machinery spaces, or control spaces shall be separate from the branch ...
National Electrical Code 2017 of Illinois > 6 Special Equipment > 620 Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts > 620.23 Branch Circuits for Machine Room or Control Room/Machinery Space or Control Space Lighting and Receptacle(s) > (A) Separate Branch Circuits
(A) Special Equipment, Separate Branch Circuits
The branch circuit(s) supplying the lighting for machine rooms, control rooms, machinery spaces, or control spaces shall be separate from the branch ...
National Electrical Code 2020 of Illinois > 6 Special Equipment > 620 Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts > 620.23 Branch Circuits for Machine Room or Control Room/Machinery Space or Control Space Lighting and Receptacle(s) > (A) Separate Branch Circuits
27.5.3.6 Plans and Calculations,
Where sprinklers are installed above and below ceilings and such sprinklers are supplied from a common set of branch lines or separate branch lines ...