[F] 2702.2.16 Semiconductor Fabrication Facilities
Go To Full Code Chapter
Emergency power shall be provided for semiconductor fabrication facilities as required in Section 415.11.11.
Related Code Sections
26.23 Special Occupancy Requirements, Semiconductor Fabrication Facilities
pipe automatic sprinkler protection shall be provided throughout facilities containing cleanrooms and clean zones. [318:11.1.4.1 ...
2702.2.15 Electrical, Semiconductor Fabrication Facilities
Emergency power shall be provided for semiconductor fabrication facilities as required in Section 415.11.10 ...
2702.2.16 Electrical, Semiconductor Fabrication Facilities
Emergency power shall be provided for semiconductor fabrication facilities as required in Section 415.11.11 ...
26.23.1.3 Special Occupancy Requirements,
Sprinklers installed in duct systems shall be hydraulically designed to provide 0.5 gpm (1.9 L/min) over an area derived by multiplying the distance ...
26.23.1.3.1* Special Occupancy Requirements,
Minimum discharge shall be 20 gpm (75 L/min) per sprinkler from the five hydraulically most remote sprinklers. [318:11.2.1.2.1 ...